beautypg.com

Fault reporting in integer mode – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 183

background image

Publication 1756-UM009C-EN-P - December 2010

183

Isolated Analog Output Modules (1756-OF6CI and 1756-OF6VI) Chapter 8

Fault Reporting in
Integer Mode

The illustration offers an overview of the fault reporting process in
integer mode.

15

14

13

12

11

5

4

3

2

1

0

15 = AnalogGroupFault
13 = OutGroupFault
12 = Calibrating
11 = Cal Fault
14 is not used by the
1756-OF6CI or
1756-OF6VI.

5 = Ch5Fault
4 = Ch4Fault
3 = Ch3Fault
2 = Ch2Fault
1 = Ch1Fault
0 = Ch0Fault

Output in Hold conditions
must be monitored here.

5

4

9

8

7

6

15

14

13

12

11

10

14 = Ch0InHold
12 = Ch1InHold
10 = Ch2InHold
8 = Ch3InHold
6 = Ch4InHold
4 = Ch5InHold

15, 13, 11, 9, 7, & 5
are not used by the
1756-OF6CI and
1756-OF6VI in
integer mode.

If set, any bit in the Channel Fault word, also sets the Analog
Group Fault and Output Group Fault in the Module Fault word.

When the module is calibrating, all bits
in the Channel Fault word are set.

Module Fault Word

(described on

page 184

)

Channel Fault Word

(described on

page 184

)

Channel Status Words

(described on

page 185

)

41349