Power dissipation, max

Voltage: 1.73 W
Current: 2.33 W

Thermal dissipation

Voltage: 5.88 BTU/hr
Current: 7.92 BTU/hr

Input impedance

Voltage: >1 M

Ω

Current: 249

Ω

Open circuit detection time

Differential voltage: Positive full scale reading within 5 s
Single-ended/diff. current: Negative full scale reading
within 5 s
Single-ended voltage: Even numbered channels go to
positive full scale reading within 5 s, odd numbered
channels go to negative full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC
Current: 8V DC

Normal mode noise rejection

>80 dB @ 50/60 Hz

(1)

Common mode noise rejection

>100 dB @ 50/60 Hz

Calibrated accuracy 25 °C

Voltage: Better than 0.05% of range
Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

45

μ

V/°C

Gain drift with temperature

Voltage: 15 ppm/°C
Current: 20 ppm/°C

Module error

Voltage: 0.1% of range
Current: 0.3% of range

Module input scan time, min

8 pt single-ended (floating point): 16…488 ms
4 pt differential (floating point): 8…244 ms
2 pt differential (floating point): 5…122 m

(1)

Isolation voltage

250V (continuous), reinforced insulation type,
inputs-to-backplane
No isolation between individual inputs

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

1

Wire size

0.33…2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max

(2)

Wire category

2

(3)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.