Analog I/O Module Specifications Appendix A
Settling time
< 2 ms to 95% of final value with resistive loads
Calibrated accuracy
4…21 mA: better than 0.1% of range @ 25 °C (77 °F)
Calibration interval
6 months
Offset drift
60
μ
V/ °C
Gain drift with temperature
50 ppm/°C, 80 ppm/°C max
Module error
0.5% of range
Module scan time
25 ms floating point
10 ms integer
Isolation voltage
250V (continuous), basic insulation type, output
channels-to-backplane, and output channel-to-channel
Routine tested at 1350V AC for 2 s
Removable terminal block
1756-TBNH
1756-TBSH
Slot width
1
Wire size
0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper
wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max
(1)
Wire category
2
(2)
North American temperature code
T4A
IEC temperature code
T4
Enclosure
None (open-style)
(1)
Maximum wire size requires extended housing, catalog number 1756-TBE.
(2)
Use this conductor category information for planning conductor routing as described in the system-level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication
Technical Specifications - 1756-OF6VI
Attribute
1756-OF6VI
Environmental Specifications - 1756-OF6VI
Attribute
1756-OF6VI
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air
60 °C (140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges