beautypg.com

Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 321

background image

Publication 1756-UM009C-EN-P - December 2010

321

Analog I/O Module Specifications Appendix A

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy

4…21 mA: better than 0.1% of range @ 25 °C (77 °F)

Calibration interval

6 months

Offset drift

60

μ

V/ °C

Gain drift with temperature

50 ppm/°C, 80 ppm/°C max

Module error

0.5% of range

Module scan time

25 ms floating point
10 ms integer

Isolation voltage

250V (continuous), basic insulation type, output
channels-to-backplane, and output channel-to-channel

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

1

Wire size

0.33…2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max

(1)

Wire category

2

(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure

None (open-style)

(1)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Technical Specifications - 1756-OF6VI

Attribute

1756-OF6VI

Environmental Specifications - 1756-OF6VI

Attribute

1756-OF6VI

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air

60 °C (140 °F)

Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)

5…95% noncondensing

Vibration
IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11: Group 1, Class A

ESD Immunity
IEC 61000-4-2

6 kV contact discharges
8 kV air discharges