Module error at 25 °c (77 °f) (-12…30 mv range) – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual
Page 367

Publication 1756-UM009C-EN-P - December 2010
367
Additional Specification Information Appendix E
Module Error at 25 °C (77 °F) (-12…30 mV Range)
The table lists the ControlLogix thermocouple modules’ error at 25 °C (77 °F)
when used in the -12…30 mV input range.
The information represented in the table is shown graphically in the following
illustrations.
Application
Temperature
Module Error (in degrees) at 25 °C (77 °F) When Connected to This Thermocouple Type
B
R
S
E
(1)
J
(2)
K
(3)
N
(4)
T
-200 °C (-328 °F)
0.836
0.96
1.376
2.115
1.334
0 °C (32 °F)
0.358
0.42
0.532
0.803
0.542
200 °C (392 °F)
2.37
2.48
0.284
0.38
0.525
0.637
0.395
400 °C (752 °F)
2.02
2.19
0.262
0.38
0.497
0.566
0.340
600 °C (1112 °F)
3.53
1.85
2.06
0.494
0.539
800 °C (1472 °F)
2.75
1.71
1.93
0.535
1000 °C (1832 °F)
2.30
1.59
1.82
1200 °C (2192 °F)
2.03
1.51
1.75
1400 °C (2552 °F)
1.86
1.49
1.73
1600 °C (2919 °F)
1.80
1.51
1.77
1800 °C (3272 °F)
1.83
1.71
2.04
(1)
Type E thermocouples can only be used in applications up to 400 °C (752 °F).
(2)
Type J thermocouples can only be used in applications up to 550 °C (1022 °F).
(3)
Type K thermocouples can only be used in applications up to 700 °C (1292 °F).
(4)
Type N thermocouples can only be used in applications up to 800 °C (1472 °F).
Application Temperature in °C
0.00
1.00
2.00
3.00
-200
0
200
400
600
800
1000
1200
1400
1600
1800
Module Error (+/-)
Thermocouple Module Error at 25 °C (77 °F)
- Type B Thermocouple Connection in a -12…30 mV Input Range
45092