Chapter 7 Non-isolated Analog Output Modules (1756-OF4 and 1756-OF8)
Choose a Data Format
Data format defines the format of channel data sent from the controller to the
module, defines the format of the ‘data echo’ that the module produces, and
determines the features that are available to your application. You choose a
data format when you choose a
You can choose one of these data formats:
• Integer mode
• Floating point mode
The table shows features that are available in each format.
For details on input and output data formats, see
in
Non-isolated Output
Module Features
The table lists features that are specific to the non-isolated analog
output modules.
You can mix current and voltage outputs on a 1756-OF4 or
1756-OF8 module. Other common features are described in the
following pages.
Features Available in Each Data Format
Data Format
Features Available
Features Not Available
Integer mode
Ramp to program value
Ramp to fault value
Hold for initialization
Hold Last State or User Value in
fault or program mode
Clamping
Ramp in Run mode
Rate and Limit alarms
Scaling
Floating point mode
All features
N/A