(4) Brake ON Timing after the Servomotor Stops

When the servomotor stops, the /BK signal turns OFF at the same time as the SV_OFF command is received.

Use parameter Pn506 to change the timing to turn OFF the servomotor power after the SV_OFF command has
been received.

Pn506

Brake Reference-Servo OFF Delay Time

 

 

 

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 50

10 ms

0

Immediately

Setup

Speed

Position

Torque

• When using the servomotor to control a vertical

axis, the machine movable part may shift slightly

depending on the brake ON timing due to gravity or
an external force. To eliminate this slight shift, set

parameter so that the power to the servomotor turns

OFF after the brake is applied.

• This parameter changes the brake ON timing while

the servomotor is stopped.

SV_OFF
command

/BK output

Power to motor

Brake released

(ON)

Servo ON

Power to motor

Brake applied

(OFF)

Servo OFF

No power to motor

Pn506

MECHA

The servomotor will turn OFF immediately when an alarm occurs, regardless of the set-
ting of this parameter. The machine movable part may shift due to gravity or external
force before the brake operates.