3 Wiring and Connection

3.7.1 Wiring for Noise Control

3-26

(1) Noise Filter

The SERVOPACK has a built-in microprocessor (CPU), so protect it from external noise as much as possible

by installing a noise filter in the appropriate place.

The following is an example of wiring for noise control.

∗1.

For ground wires connected to the ground plate, use a thick wire (preferably, plain stitch cooper wire).

∗2.

should be twisted-pair wires.

∗3.

When using a noise filter, follow the precautions in

3.7.2 Precautions on Connecting Noise Filter

.

(2) Correct Grounding

Take the following grounding measures to prevent the malfunction due to noise.

Grounding the Motor Frame

Always connect servomotor frame terminal FG to the SERVOPACK ground terminal . Also be sure to
ground the ground terminal .

If the servomotor is grounded via the machine, a switching noise current will flow from the SERVOPACK

main circuit through servomotor stray capacitance. The above grounding is required to prevent the adverse
effects of switching noise.

Noise on the I/O Signal Cable

If the I/O signal cable receives noise, ground the 0 V line (SG) of the I/O signal cable. If the servomotor main
circuit cable is accommodated in a metal conduit, ground the conduit and its junction box. For all grounding,

ground at one point only.

U

V

W

M

(FG)

CN4

ENC

CN2

CN1

CN3

C2

C1

L2

L1

Non-isolated AC/DC converter
for main circuit power supply

Non-isolated AC/DC converter
for control power supply

AC power
supply

*3

*1

AC/DC converter

*3

*2

*2

*2

0.5 mm

2

SERVOPACK

Operation relay sequence
Signal generation
circuit (not included)

(Ground plate)

Noise filter

Noise filter

Ground: Ground to an independent ground

2.0 mm

2

min.

2.0 mm

2

min.

2.0 mm

2

min.

2.0 mm

2

min.