8 Troubleshooting

8.1.2 Troubleshooting of Alarms

8-6

A.042:
Parameter

Combination Error

The speed of program JOG oper-
ation (Fn004) is lower than the
setting range after having
changed the electronic gear ratio
(Pn20E/Pn210) or the servomo-
tor.

Check if the detection conditions

*1

are satisfied.

Decrease the setting of the elec-
tronic gear ratio (Pn20E/Pn210).

The speed of program JOG oper-
ation (Fn004) is lower than the
setting range after having

changed the setting of the pro-
gram JOG movement speed
(Pn533).

Check if the detection conditions

*1

are satisfied.

Increase the setting of the program

JOG movement speed (Pn533).

The moving speed of advanced
autotuning is lower than the set-
ting range after having changed
the electronic gear ratio (Pn20E/
Pn210) or the servomotor.

Check if the detection conditions

*2

are satisfied.

Decrease the setting of the elec-
tronic gear ratio (Pn20E/Pn210).

A.04A:
Parameter Setting

Error 2

For a 4-byte parameter bank, no
registration in two consecutive
bytes for two bank members.

Change the number of bytes for
bank members to an appropriate
value.

The total amount of bank data
exceeds 64. (Pn900

×

Pn901 >

64)

Reduce the total amount of bank
data to 64 or less.

A.050:
Combination Error

(The SERVOPACK and
servomotor capacities do
not correspond.)

The SERVOPACK and servomo-
tor capacities do not match each
other.

Check the capacities to see if they
satisfy the following condition:

Select the proper combination of
SERVOPACK and servomotor
capacities.

An encoder fault occurred.

Replace the servomotor and see if
the alarm occurs again.

Replace the servomotor (encoder).

A SERVOPACK fault occurred.

The SERVOPACK may be faulty.
Replace the SERVOPACK.

A.051:
Unsupported Device

Alarm

An unsupported encoder is con-
nected to the SERVOPACK.

Check the product specifications,
and select the correct model.

Select the correct combination of
units.

A.0b0:
Cancelled Servo ON

Command Alarm

After executing the utility func-
tion to turn ON the power to the
motor, the servo ON command
(SV_ON) was sent from the host
controller.

Restart the SERVOPACK or exe-
cute a software reset.

∗1.

Detection conditions
If one of the following conditions detected, an alarm occurs.

∗2.

Detection conditions
If one of the following conditions detected, an alarm occurs.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions

Servomotor capacity

SERVOPACK capacity

4

1
4

Pn533 [min

-1

]

Ч

6

Ч

10

5

Encoder resolution

Pn20E
Pn210

Max Motor Speed [min

-1

]

×

About 3.66

×

10

12

Encoder resolution

Pn20E
Pn210

Rated Motor Speed [min

-1

]

Ч

6

Ч

10

5

Encoder resolution

Pn20E
Pn210

×

1
3

Max Motor Speed [min

-1

]

×

About 3.66

×

10

12

Encoder resolution

Pn20E
Pn210