6 Utility Functions (Fn

)

6-24

6.10

Automatic Offset-Signal Adjustment of the Motor Current

Detection Signal (Fn00E)

Perform this adjustment only if highly accurate adjustment is required for reducing torque ripple caused by

current offset. The user need not usually use this function.

Note: The adjusted value is not initialized by executing the Fn005 function (Initializing Parameter Settings).

(1) Preparation

The following conditions must be met to automatically adjust the offset of the motor current detection signal.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The SERVOPACK must be in Servo Ready status (Refer to

4.8.4

).

• The servomotor power must be OFF.

(2) Operating Procedure

Use the following procedure.

1.

In the SigmaWin+ main window, click

Setup

-

Adjust Offset - Adjust the Motor Current

Detection Offset

.

The following message will appear and ask if you want to continue. The message informs you that the

offset is set to the factory settings and that the SERVOPACK's performance might be affected if these set-
tings are changed.

• Be sure to perform this function while the servomotor power is OFF.
• Execute the automatic offset adjustment if the torque ripple is too big when compared

with those of other SERVOPACKs.