5.2 Tuning-less Function

5-13

5

Adjustments

5.2.2

Tuning-less Levels Setting (Fn200) Procedure

The procedure to use the tuning-less function is given below.

The SigmaWin+ is required to execute this function.

(1) Preparation

The following conditions must be met to perform the tuning-less function.

• The tuning-less function must be enabled (Pn170.0 = 1).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The test without a motor function must be disabled. (Pn00C.0 = 0).

(2) Operating Procedure

Use the following procedure.

1.

In the SigmaWin+ main window, click

Parameters

-

Edit Parameters

.

The

Parameter Editing

dialog box will appear.

CAUTION

• To ensure safety, perform the tuning-less function in a state where the SERVOPACK can come to an

emergency stop at any time.