Yaskawa Σ-V Series AC Servo Drives Rotational Motor MECHATROLINK-III User Manual
Page 125
5.2 Tuning-less Function
5-15
5
Adjustments
4.
For 3rd digit, select one of the load levels in the
Tuning-less Load Level
list.
• If the response waveform results in overshooting or if the load moment of inertia exceeds the allowable
level, select
2: Tuning-less Load Level 2
. (If any damage caused when the load moment of inertia
exceeds the allowable level, these conditions are regarded as being outside the scope of the warranty.)
• If a high-frequency noise is heard, select
0: Tuning-less Load Level 0
.
5.
For 2nd digit, select one of the tuning-less levels in the
Tuning-less Level
list.
The higher the value of the level is, the higher the gain will be. A higher gain means better response.
Note 1. If the tuning-less level is too high, vibration might occur. Lower the level if vibration occurs.
2. If the tuning-less level is changed, the automatically set notch filter will be canceled (disabled). If any
vibration occurs, the notch filter will automatically be set again.
6.
Click
OK
.
7.
To enable the change in the setting, restart the SERVOPACK.