6.7 Clearing Alarm History (Fn006)

6-19

6

Utili

ty Fu

ncti

ons (Fn

)

6.7

Clearing Alarm History (Fn006)

The clear alarm history function deletes all of the alarm history recorded in the SERVOPACK.

Note: The alarm history is not deleted when the alarm reset is executed or the main circuit power supply of the SERVO-

PACK is turned OFF.

(1) Preparation

The follow conditions must be met to clear the alarm history.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).

(2) Operating Procedure

Use the following procedure.

1.

In the SigmaWin+ main window, click

Alarm

-

Display Alarm

.

The

Alarm Display

box will appear.

2.

Click the

Alarm traceback

tab.

3.

Click

Clear

.

The alarm history will be cleared.