This section describes the switch settings necessary for MECHATROLINK-III communications.

4.1.1

Setting Switches S1 and S2

The S2 DIP switch is used to make the settings for MECHATROLINK-III communications.

The S1 DIP switch is used to make the settings for the station address.

(1) Settings of the S2 DIP Switch

The following table shows the settings of the S2 DIP switch.

OFF

ON

S1 (factory settings)

1

2

3

4

5

6

7

8

OFF

ON

S2 (factory settings)

1

2

3

4

M-III

S2

Function

Setting

Factory

setting

1

2

Number of transmission

bytes

Pins 1 and 2

Sets the number of

transmission bytes.

OFF

OFF

16 bytes

1: OFF

2: ON

ON

OFF

32 bytes

OFF

ON

48 bytes

ON

ON

Reserved.
(Do not use this setting.)

Pin 3

Reserved. (Do not change.)

OFF

Pin 4

Reserved. (Do not change.)

OFF

• When using the MECHATROLINK-III standard servo profile, set the number of transmission bytes to

either 32 or 48.

• When using the MECHATROLINK-II-compatible profile, set the number of transmission bytes to either

16 or 32.

• To enable the change in the setting, restart the SERVOPACK.