Nt8d22 system monitor, Table 36 nt8d22 sw1 – Nortel Networks Circuit Card 311 User Manual
Page 97

NT8D22 System Monitor
97
Settings
Frequency
Amplitude
P1
P2
P3
25 Hz
86 V ac
open
2–5
8–11
open
50 Hz
70 V ac
1–4
7–10
open
open
50 Hz
80 V ac
3–6
9–12
open
open
NT8D22 System Monitor
The master system monitor, located in the column with CP 0, must be
numbered 0. Slave system monitors are numbered from 1 to 63.
For examples of system monitor option settings in basic configurations, see
"Sample settings for NT8D22 System Monitors."
Configure the system monitor in Remote Peripheral Equipment (RPE)
columns as slaves. There is no serial connection between RPE columns.
Table 36
NT8D22 SW1
Position
SW1 function
1
2
3
4
5
6
7
8
Not used
Meridian 1 columns only
on
off
Position 1 is OFF (Meridian 1
columns only)
Not used
Position 1 is ON, master column
contains CP:master
slaves
off
off
on
off
DC-powered system
AC-powered system
on
off
PFTU is activated by this column
due to over-temperature
PFTU is not activated by this
column
on
off
Position 1 is OFF (Meridian 1
columns only)
Not used
Not used
off
on
off
Nortel Communication Server 1000
Circuit Card Reference
NN43001-311
01.04
Standard
Release 5.0
23 May 2008
Copyright © 2003-2008, Nortel Networks
.