3.8 Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in

the drive.

NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices

could result in drive malfunction due to loose terminal connections.

NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus

charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the

drive on and off more than once every 30 minutes.

u

Main Circuit Terminal Functions

Table 3.2 Main Circuit Terminal Functions

Drive Model

2o0028 to 2o0248

4o0011 to 4o0414

Function

Page

Terminal

Type

R/L1

Main circuit power supply input

Connects line power to the drive

57

S/L2

T/L3
U/T1

Drive output

Connects to the motor

57

V/T2

W/T3

p1, n1

Momentary power loss recovery unit input

Available for connecting a momentary power

loss recovery unit option

100 Ω or less

10 Ω or less

Grounding terminal

77

3.8 Main Circuit Wiring

70

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual