No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-11

(01AF)

PID Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

150

b5-12

(01B0)

PID Feedback Loss

Detection Selection

Fb loss Det Sel

0: Disabled

1: Alarm @ PID Enbl

2: Fault @ PID Enbl

3: DO Only@PID

Enbl

4: Alarm – Always

5: Fault – Alwaysl

0: Digital Output Only

(Remains active when PID is disabled by digital input)

1: Alarm output, drive continues operation (Remains active

when PID is disabled by digital input)

2: Fault output, drive output is shut off (Remains active when

PID is disabled by digital input)

3: Digital output only. No detection when PID is disabled by

digital input.

4: Alarm detection. No detection when PID is disabled by digital

input.

5: Fault detection. No detection when PID is disabled by digital

input.

Default: 0

Range: 0 to 5

150

b5-13

(01B1)

PID Feedback Loss

Detection Level

Fb loss Det Lvl

Sets the PID feedback loss detection level as a percentage of the

maximum output frequency.

Default: 0%

Min.: 0

Max.: 100

151

b5-14

(01B2)

PID Feedback Loss

Detection Time

Fb loss Det Time

Sets a delay time for PID feedback loss.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

151

b5-15

(01B3)

PID Sleep Function Start

Level

PID Sleep Level

Sets the frequency level that triggers the sleep/snooze function. Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

151

b5-16

(01B4) PID Sleep Delay Time

PID Sleep Time

Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s

Min.: 0.0

Max.: 25.5

151

b5-17

(01B5) PID Accel/Decel Time PID Acc/Dec Time

Sets the acceleration and deceleration time to PID setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

151

b5-18

(01DC) PID Setpoint Selection

PID Setpoint Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

151

b5-19

(01DD) PID Setpoint Value

PID Setpoint

Sets the PID target value when b5-18 = 1. Set as a percentage

of the maximum output frequency.

Default: 0.00%

Min.: 0.00
Max.: 100.00

<1>

151

b5-20

(01E2) PID Setpoint Scaling

PID Disp Scaling

0: 0.01Hz units

1: 0.01% units

2: r/min

3: User Units

0: 0.01 Hz units

1: 0.01% units (100% = max output frequency)

2: r/min (number of motor poles must entered)

3: User-set (set scaling to b5-38 and b5-39)

Default: 1

Range: 0 to 3

152

b5-21

(01E3) PID Sleep Input Source

PID Sleep Ref

0: PID Setpoint

1: Frequency Ref

2: Snooze Func

Input source selection for Sleep Function mode.

0: PID Setpoint

1: SFS Input

2: Snooze

Default: 1

Range: 0 to 2

152

b5-22

(01E4) PID Snooze Level

Snooze Level

Sets the PID Snooze Function start level as a percentage of the

maximum frequency.

Default: 0%

Min.: 0

Max.: 100

152

b5-23

(01E5) PID Snooze Delay Time Snooze DelayTime

Sets the PID Snooze Function delay time in seconds.

Default: 0s

Min.: 0

Max.: 2600

152

b5-24

(01E6)

PID Snooze

Deactivation Level

SnoozeRestartLvl

When the PID feedback level drops below this level, the drive

returns to normal operation. Set as a percentage of the maximum

frequency.

Default: 0%

Min.: 0

Max.: 100

152

b5-25

(01E7)

PID Setpoint Boost

Setting

SetpointBoostLvl

Temporarily increases the PID setpoint to create an overshoot

of the intended PID setpoint.

Default: 0%

Min.: 0

Max.: 100

152

b5-26

(01E8)

PID Maximum Boost

Time

SetpointBoostTim

Sets the maximum boost time when PID feedback does not

reach boost level.

The Snooze Function starts when the PID feedback exceeds the

boost setting level or when the boost time expires.

Default: 0s

Min.: 0

Max.: 2600

153