Mechanical installation, Installation environment, Installation orientation and spacing – Yaskawa Z1000U User Manual
Page 42: 2 mechanical installation

2.2 Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
u
Installation Environment
Install the drive in an environment matching the specifications in
to help prolong the optimum performance life of
the drive.
Table 2.1 Installation Environment
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10 °C to +50 °C (14 °F to 122 °F)
IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity
95% RH or less and free of condensation
Storage Temperature
-20 °C to +60 °C (-4 °F to +104 °F)
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating
Vibration
10 to 20 Hz at 9.8 m/s
2
(32.15 ft/s
2
)
20 to 55 Hz at 5.9 m/s
2
(19.36 ft/s
2
) (Models 2o0028 to 2o0081 and 4o0011 to 4o0077)
2.0 m/s
2
(6.56 ft/s
2
) (Models 2o0104 to 2o0248 and 4o0096 to 4o0414)
Orientation
Install the drive vertically to maintain maximum cooling effects.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous
operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply
could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before
drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
u
Installation Orientation and Spacing
NOTICE: Install the drive upright as illustrated in
. Failure to comply may damage the drive due to improper cooling.
Figure 2.1 Correct Installation Orientation
NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.
n
Single Drive Installation
shows the installation distance required to maintain sufficient space for airflow and wiring.
2.2 Mechanical Installation
42
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual