Setting 1: Number of Run Commands Counter

Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the

counter value and returns the display to 0.

n

o4-17: Set/Reset Real Time Clock

The time setting screen will appear.

No.

Name

Setting Range

Default

o4-17

Set/Reset Real Time Clock

0 to 2

0

Setting 0: — —

No Setting

Setting 1: Set

The HOA keypad shows the Clock Adjustment display. In Clock Adjustment Mode the user can adjust the Real Time Clock.

Setting 2: Reset

The Real-Time Clock data is cleared. A TIM fault will occur until o4-17 is set to 1 to set the Real Time Clock.

n

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used.

Refer to Auto-Tuning for Induction Motors on page 131

for details on the different

types of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2, 3

2

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving

n

T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Note:

Use the following formula to convert HP to kW: kW = HP x 0.746.

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

n

T1-03: Motor Rated Voltage

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates

above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 255.0 V

<1>

200.0 V

<1>

<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives.

n

T1-04: Motor Rated Current

Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10.0 to 150.0% of drive rated

current

Determined by

o2-04

n

T1-05: Motor Base Frequency

Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or

the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 400.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles

Sets the number of motor poles according to the motor nameplate value.

4.12 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

179

4

Start-Up Programming & Operation