beautypg.com

D7: offset frequency – Yaskawa Z1000U User Manual

Page 267

background image

u

d7: Offset Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Setting

Page

d7-01

(02B2) Offset Frequency 1

Offset Freq 1

Added to the frequency reference when the digital input

“Frequency offset 1” (H1-oo = 44) is switched on.

Default: 0.0%

Min.: -100.0

Max.: 100.0

d7-02

(02B3) Offset Frequency 2

Offset Freq 2

Added to the frequency reference when the digital input

“Frequency offset 2” (H1-oo = 45) is switched on.

Default: 0.0%

Min.: -100.0

Max.: 100.0

d7-03

(02B4) Offset Frequency 3

Offset Freq 3

Added to the frequency reference when the digital input

“Frequency offset 3” (H1-oo = 46) is switched on.

Default: 0.0%

Min.: -100.0

Max.: 100.0

B.5 d: References

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

267

B

Parameter List

This manual is related to the following products: