U6: operation status monitors, U9: power monitors, Parameters – Yaskawa Z1000U User Manual
Page 316
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U5-18
(302B) PI2 Feedback
PI2 Feedback
Displays the secondary PI feedback value.
10 V: Max
frequency
0.01%
U5-19
(302C) PI2 Input
PI2 Input
Displays the secondary PI input (deviation between PID target
and feedback).
10 V: Max
frequency
0.01%
U5-20
(302D) PI2 Output
PI2 Output
Displays the secondary PI control output.
10 V: Max
frequency
0.01%
U5-30
(3000)
Time Hr Min HHMM
Time Hr Min HHMM Displays the current time (Hours and Minutes).
No signal output
available
1
U5-31
(3001)
Date Year
Date Year
Displays the current year.
No signal output
available
1
U5-32
(3002)
Date Mo Day MMDD
Date Mo Day MMDD Displays the current date (Month and Day).
No signal output
available
1
U5-33
(3003)
Day of the Week
Date Week
0: Sun
1: Mon
2: Tues
3: Wed
4: Thur
5: Fri
6: Sat
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
1
<1> Analog Output selection text is: “PID Output 2”.
u
U6: Operation Status Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U6-01
(0051)
Motor Secondary
Current (Iq)
Mot SEC Current
Displays the value of the motor secondary current (Iq). Motor
rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-02
(0052)
Motor Excitation
Current (Id)
Mot EXC Current
OLV/PM
OLV/PM
Displays the value calculated for the motor excitation current (Id).
Motor rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-05
(0059)
Output Voltage
Reference (Vq)
Voltage Ref (Vq)
OLV/PM
OLV/PM
Output voltage reference (Vq) for the q-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-06
(005A)
Output Voltage
Reference (Vd)
Voltage Ref (Vd)
OLV/PM
OLV/PM
Output voltage reference (Vd) for the d-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-21
(07D5) Offset Frequency
Offset Frequency
Displays the frequency added to the main frequency reference.
–
0.1%
U6-80 to
U6-99
(07B0 to
07F9)
Option Monitors 1 to
20
–
Output monitor for option card.
Refer to Option Instruction manual for details
No signal output
available.
–
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives.
u
U9: Power Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U9-01
(0820) Electric Power (GWh)
GWh Consumed
Shows the total amount of electric power.
000 000 000 kW
U9-03
U9-02
U9-01
No signal output
available
1 GWh
U9-02
(0821) Electric Power (MWh)
MWh Consumed
No signal output
available
1 MWh
U9-03
(0822) Electric Power (kWh)
kWh Consumed
No signal output
available
1 kWh
B.14 U: Monitors
316