B.6 E: Motor Parameters

u

E1: V/f Pattern for Motor 1

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E1-03

(0302)

V/f Pattern Selection

V/F Selection

0: 50 Hz

1: 60 Hz Saturation

2: 60 Hz Saturation

3: 72 Hz

4: 50 Hz VT1

5: 50 Hz VT2

6: 60 Hz VT1

7: 60 Hz VT2

8: 50 Hz HST1

9: 50 Hz HST2

A: 60 Hz HST1

B: 60 Hz HST2

C: 90 Hz

D: 120 Hz

E: 180 Hz

F: Custom V/F

0: 50 Hz, Constant torque 1

1: 60 Hz, Constant torque 2

2: 60 Hz, Constant torque 3 (50 Hz base)

3: 72 Hz, Constant torque 4 (60 Hz base)

4: 50 Hz, Variable torque 1

5: 50 Hz, Variable torque 2

6: 60 Hz, Variable torque 3

7: 60 Hz, Variable torque 4

8: 50 Hz, High starting torque 1

9: 50 Hz, High starting torque 2

A: 60 Hz, High starting torque 3

B: 60 Hz, High starting torque 4

C: 90 Hz (60 Hz base)

D: 120 Hz (60 Hz base)

E: 180 Hz (60 Hz base)

F: Custom V/f E1-04 through E1-13 settings define the V/f

pattern

Default: F

<1>

Range: 0 to 9;

A to F

159

E1-04

(0303)

Maximum Output

Frequency

Max Frequency

These parameters are only applicable when E1-03 is set to F.

To set linear V/f characteristics, set the same values for E1-07

and E1-09.

In this case, the setting for E1-08 will be disregarded. Ensure

that the four frequencies are set according to these rules:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

Note:

E1-07, E1-08, and E1-10 to E1-13 are not

available in OLV/PM control mode.

Default:

<2> <8>

Min.: 40.0 Hz
Max.: 400.0 Hz

<3>

121

E1-05

(0304)

<7>

Maximum Voltage

Max Voltage

Default:

<2> <4>

Min.: 0.0 V
Max.: 255.0 V

<5>

121

E1-06

(0305)

Base Frequency

Base Frequency

Default:

<2> <4>

<8>

Min.: 0.0 Hz
Max.: E1-04

<3>

121

E1-07

(0306)

Middle Output

Frequency

Mid Frequency A

Default:

<2>

Min.: 0.0 Hz

Max.: E1-04

121

E1-08

(0307)

Middle Output

Frequency Voltage

Mid Voltage A

Default:

<2>

Min.: 0.0 V
Max.: 255.0 V

<5>

121

E1-09

(0308)

Minimum Output

Frequency

Min Frequency

Default:

<2> <4>

<8>

Min.: 0.0 Hz
Max.: E1-04

<3>

121

E1-10

(0309)

Minimum Output

Frequency Voltage

Min Voltage

Default:

<2>

Min.: 0.0 V
Max.: 255.0 V

<5>

121

E1-11

(030A)

<6>

Middle Output

Frequency 2

Mid Frequency B

Default: 0.0 Hz

Min.: 0.0

Max.: E1-04

121

E1-12

(030B)

<6> <9>

Middle Output

Frequency Voltage 2

Mid Voltage B

Default: 0.0 V

Min.: 0.0
Max.: 255.0

<5>

121

E1-13

(030C)

<7> <9>

Base Voltage

Base Voltage

Default: 0.0 V

Min.: 0.0
Max.: 255.0

<5>

121

<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting is dependent on parameters A1-02, Control Mode Selection and o2-04, Drive Model Selection.
<3> Default setting is determined by E5-01 in OLV/PM.

When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 400.0 Hz and the setting range for E1-09 is 0.0 to 400.0 Hz.

B.6 E: Motor Parameters

268

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual