Yaskawa Z1000U User Manual
Page 103

Step
Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
2. Press
or
until the Parameter Setting Mode screen appears.
HELP
- MODE -
PRG
DATA
Programming
FWD
3. Press
to enter the parameter menu tree.
←
→
-PRMSET-
Initialization
Select Language
PRG
FWD
A
1-00= 0
4. Press
or
to select the C parameter group.
←
→
-PRMSET-
Basic Setup
Accel Time 1
PRG
FWD
C
1-01=
30.0 sec
5. Press
two times.
-PRMSET-
Accel/Decel
Accel Time 1
PRG
C
1
-01=
30.0 sec
-PRMSET-
C1-
01
= 30.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Accel Time 1
←
→
FWD
←
→
FWD
6. Press
or
to select parameter C1-02.
-PRMSET-
C1-
02
= 30.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
7. Press
to view the current setting value. The leftmost digit flashes.
-PRMSET-
C1-02=
0
030.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
8. Press
F1
,
F2
, or
until the desired number is selected. “3” flashes.
-PRMSET-
C1-02=00
3
0.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
9. Press
to enter 0020.0.
-PRMSET-
C1-02=00
2
0.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
10. Press
to confirm the change.
Entry Accepted
11. The display automatically returns to the screen shown in Step 4.
-PRMSET-
C1-
02
= 20.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
12. Press
as many times as necessary to return to the initial display.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
4.3 The Drive, Programming, and Clock Adjustment Modes
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
103
4
Start-Up Programming & Operation