background image

4.6 Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these

Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to values

appropriate for the application that was selected.
An Application Preset can either be selected from the Application Selection display in the Setup Group (

Refer to Using the

Setup Group on page 105

) or in parameter A1-06. The following presets can be selected:

Note:

An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to initialize

the drive by setting A1-03 to “2220” or “3330” prior to selecting an Application Preset.

WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the

I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.

No.

Parameter Name

Setting Range

Default

A1-06

Application Presets

0: Standard

1: Fan

2: Fan with PID Control

3: Return Fan with PID Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PID

Control

6: Pump (Secondary)

7: Pump with PID Control

0

u

HVAC Application Parameters

In addition, the application parameters most likely to be changed for fan and pump applications are assigned to the group of

User Parameters, A2-01 through A2-32. User Parameters provide quicker access to by eliminating the need to scroll through

multiple menus.

Table 4.7 User Parameters (A2-01 to A2-32)

No.

Parameter Name

b1-03

Stopping Method Selection

b1-04

Reverse Operation Selection

b2-09

Motor Pre-Heat Current 2

b5-01

PID Function Setting

b5-03

Integral Time Setting (I)

b5-08

PID Primary Delay Time Constant

b5-09

PID Output Level Selection

b5-13

PID Feedback Low Detection Level

b5-14

PID Feedback Low Detection Time

b5-15

PID Sleep Function Start Level

b5-16

PID Sleep Delay Time

C1-01

Acceleration Time 1

No.

Parameter Name

d2-03

Master Speed Reference Lower Limit

H1-07

Multi-Function Digital Input Terminal S7 Function

Selection

H3-01

Terminal A1 Signal Level Selection

H3-02

Terminal A1 Function Selection

H3-10

Terminal A2 Function Selection

L5-01

Number of Auto Restart Attempts

L6-01

Stall Prevention Selection during Deceleration

o1-06

User Monitor Selection Mode

o1-07

Second Line Monitor Selection

o1-08

Third Line Monitor Selection

u

Setting 1: Fan Application

Table 4.8 Fan: Parameter Settings

No.

Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

1: Reverse operation disabled

C1-01

Acceleration Time 1

60 s

L5-01

Number of Auto Restart Attempts

10

L6-01

Torque Detection Selection 1

5: UL3 at speed agree (Alarm)

4.6 Application Selection

112

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual