For descriptions of setting values – Yaskawa Z1000U User Manual
Page 281
H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function
LCD Display
Description
Page
70
Drive Enable2
Drive Enable 2
Prevents the Drive from executing a Run command until the Drive Enable2 input
is closed.
When the Drive Enable2 input is open and a Run command is closed, the drive
LCD will display “dnE”.
The drive will run when the Run and Drive Enable2 inputs are both closed. If the
Drive Enable2 input is opened while the drive is running, the drive will stop using
the method set by parameter b1-03.
–
A4
BP Customer Safeties
BP Emg Override
Closed: Indicates that customer safeties are in place.
–
A5
BP Drive/Bypass Select BP Drv/Bypss Sel
Open: Bypass mode.
Closed: Drive mode.
–
A6
BP BAS Interlock Input BP BAS Interlock
Closed: Indicates that the dampers are open
–
A7
BP Customer Safeties
BP Cust Safeties
Closed: Indicates that customer safeties are in place.
–
A8
Secondary PI Disable
(N.O.)
PI2 Disable N.O.
Closed: Disables the secondary PI controller. Output behavior depends on the
setting of S3-12.
–
A9
Secondary PI Disable
(N.C.)
PI2 Disable N.C.
Closed: Enables the secondary PI controller. Output behavior depends on the
setting of S3-12 when open.
–
AA
Secondary PI Inverse
Operation
PI2 Invert
Closed: Changes the sign of the secondary PI controller input (reverse acting PID
control).
–
AB
Secondary PI Integral
Reset
PI2 Intgrl Reset
Closed: Resets the secondary PI controller integral value.
–
AC
Secondary PI Integral
Hold
PI2 Intgrl Hold
Closed: Locks the value of the secondary PI controller integral value.
–
AD
Select Secondary PI
Parameters
Select PI2 Parms
Closed: Uses the secondary PI controller Proportional and Integral adjustments
(S3-06 and S3-07) instead of the primary PID controller Proportional and Integral
adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI
controller disabled).
Note:
This multi-function input has no effect on the secondary PI
controller. It is only used for the primary PID controller (b5-oo).
–
AE
BP Bypass Run
BP Bypass Run
Closed: Commands a Run (via closing the BP Bypass Relay multi-function output)
when in Bypass mode.
–
AF
Emergency Override
Forward Run
EmergOverrideFWD Closed: Emergency Override Forward Run
–
B0
Emergency Override
Reverse Run
EmergOverrideREV
Closed: Emergency Override Reverse Run
–
B1
Customer Safeties
CustomerSafeties
The functionality is identical to Drive Enable 2 (H1-oo = 70), except for the
following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a “SAFE” alarm if the input is open when a Run command
is present. It will not display “dnE”.
Open: Customer Safeties are open. Drive will not run. Stopping method is Coast
to Stop.
Closed: Customer Safeties are in place.
–
B2
BAS Interlock
BAS Interlock
Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The
drive displays an "inTLK" message if a Run command is present. It will not display
"dnE".
Closed: Damper interlock is closed. Drive operates normally.
Note:
The state of the BAS Interlock multi-function input has no effect on
the Emergency Override multi-function inputs (H1-oo = AF, B0).
The Emergency Override command is accepted when the BAS
Interlock digital input is open or closed.
–
B.8 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
281