H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

70

Drive Enable2

Drive Enable 2

Prevents the Drive from executing a Run command until the Drive Enable2 input

is closed.

When the Drive Enable2 input is open and a Run command is closed, the drive

LCD will display “dnE”.

The drive will run when the Run and Drive Enable2 inputs are both closed. If the

Drive Enable2 input is opened while the drive is running, the drive will stop using

the method set by parameter b1-03.

A4

BP Customer Safeties

BP Emg Override

Closed: Indicates that customer safeties are in place.

A5

BP Drive/Bypass Select BP Drv/Bypss Sel

Open: Bypass mode.

Closed: Drive mode.

A6

BP BAS Interlock Input BP BAS Interlock

Closed: Indicates that the dampers are open

A7

BP Customer Safeties

BP Cust Safeties

Closed: Indicates that customer safeties are in place.

A8

Secondary PI Disable

(N.O.)

PI2 Disable N.O.

Closed: Disables the secondary PI controller. Output behavior depends on the

setting of S3-12.

A9

Secondary PI Disable

(N.C.)

PI2 Disable N.C.

Closed: Enables the secondary PI controller. Output behavior depends on the

setting of S3-12 when open.

AA

Secondary PI Inverse

Operation

PI2 Invert

Closed: Changes the sign of the secondary PI controller input (reverse acting PID

control).

AB

Secondary PI Integral

Reset

PI2 Intgrl Reset

Closed: Resets the secondary PI controller integral value.

AC

Secondary PI Integral

Hold

PI2 Intgrl Hold

Closed: Locks the value of the secondary PI controller integral value.

AD

Select Secondary PI

Parameters

Select PI2 Parms

Closed: Uses the secondary PI controller Proportional and Integral adjustments

(S3-06 and S3-07) instead of the primary PID controller Proportional and Integral

adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI

controller disabled).

Note:

This multi-function input has no effect on the secondary PI

controller. It is only used for the primary PID controller (b5-oo).

AE

BP Bypass Run

BP Bypass Run

Closed: Commands a Run (via closing the BP Bypass Relay multi-function output)

when in Bypass mode.

AF

Emergency Override

Forward Run

EmergOverrideFWD Closed: Emergency Override Forward Run

B0

Emergency Override

Reverse Run

EmergOverrideREV

Closed: Emergency Override Reverse Run

B1

Customer Safeties

CustomerSafeties

The functionality is identical to Drive Enable 2 (H1-oo = 70), except for the

following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a “SAFE” alarm if the input is open when a Run command

is present. It will not display “dnE”.

Open: Customer Safeties are open. Drive will not run. Stopping method is Coast

to Stop.

Closed: Customer Safeties are in place.

B2

BAS Interlock

BAS Interlock

Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The

drive displays an "inTLK" message if a Run command is present. It will not display

"dnE".

Closed: Damper interlock is closed. Drive operates normally.

Note:

The state of the BAS Interlock multi-function input has no effect on

the Emergency Override multi-function inputs (H1-oo = AF, B0).

The Emergency Override command is accepted when the BAS

Interlock digital input is open or closed.

B.8 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual