Yaskawa Z1000U User Manual
Page 123

0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
2: Rated Torque for IPM
Motors
(SST4 Series)
Figure 4.23 PM Motor Code
n
E5-02: Motor Rated Power (for PM Motors)
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.
No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power (for PM Motors)
0.10 to 650.00 kW
Determined by
E5-01
n
E5-03: Motor Rated Current (for PM Motors)
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current (for PM Motors)
10 to 150% of drive rated
current
<1>
Determined by
E5-01
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units
n
E5-04: Number of Motor Poles (for PM Motors)
Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-04
Number of Motor Poles (for PM Motors)
2 to 48
Determined by
E5-01
n
E5-05: Motor Stator Resistance (r1) (for PM Motors)
Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance
manually.
No.
Parameter Name
Setting Range
Default
E5-05
Motor Stator Resistance (for PM Motors)
0.000 to 65.000 Ω
Determined by
E5-01
n
E5-06: Motor d-Axis Inductance (Ld) (for PM Motors)
Sets the d-Axis inductance in 0.01 mH units.
No.
Parameter Name
Setting Range
Default
E5-06
Motor d-Axis Inductance (for PM Motors)
0.00 to 300.00 mH
Determined by
E5-01
n
E5-07: Motor q-Axis Inductance (Lq) (for PM Motors)
Sets the q-Axis inductance in 0.01 mH units.
No.
Parameter Name
Setting Range
Default
E5-07
Motor q-Axis Inductance (for PM Motors)
0.00 to 600.00 mH
Determined by
E5-01
4.7 Basic Drive Setup Adjustments
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
123