beautypg.com

A: initialization parameters, A1: initialization, A2: user parameters – Yaskawa Z1000U User Manual

Page 255: B.2 a: initialization parameters

background image

B.2 A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor

Control Method, Password, User Parameters and more.

u

A1: Initialization

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

A1-00

(0100)

<1>

Language Selection

Select Language

0: English

1:

(Japanese)

3: Fran

çais

5: Español

6: Portuguêse

0: English

1: Japanese

3: French

5: Spanish

6: Portuguese

Default: 0

Range: 0 to 6

143

A1-01

(0101)

<2>

Access Level Selection

Access Level

0: Operation Only

1: User Parameters

2: Advanced Level

0: View and set A1-01 and A1-04.

Uo-oo parameters can also be viewed.

1: User Parameters (access to a set of parameters selected by the

user, A2-01 to A2-32)

2: Advanced Access (access to view and set all parameters)

Default: 2

Range: 0 to 2

143

A1-02

(0102)

<1>

Control Method

Selection

Control Method

0: V/F Control

5: PM OpenLoop Vect

0: V/f Control

5: Open Loop Vector Control for PM

Default: 0

Range: 0, 5

115

A1-03

(0103)

Initialize Parameters

Init Parameters

0: No Initialize

1110: User Initialize

2220: 2-Wire Initial

3330: 3-Wire Initial

3410: SELVAL

HVAC Initialize

3420: SELVAL OEM

Bypass Init

0: No initialization

1110: User Initialize (parameter values must be stored using

parameter o2-03)

2220: 2-Wire Initialization

3330: 3-Wire Initialization

3410: HVAC Initialization

3420: OEM Bypass Initialization

Default: 0

Range: 0 to 3420

144

A1-04

(0104)

Password

Enter Password

When the value set into A1-04 does not match the value set into

A1-05, parameters A1-01 through A1-03, A1-06, and A2-01

through A2-33 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-05

(0105)

Password Setting

Select Password

When the value set into A1-04 does not match the value set into

A1-05, parameters A1-01 through A1-03, A1-06, and A2-01

through A2-33 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-06

(0127)

Application Preset

Application Sel

0: General

1: Fan General

2: Fan PID

3: Fan ReturnAir/PID

4: Cooling Tower

5: CoolingTower/PID

6: Pump Secondary

7: Pump PID

0: Standard

1: Fan

2: Fan with PID Control

3: Return Fan with PID Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PID Control

6: Pump (Secondary)

7: Pump with PID Control

Default: 0

Range: 0 to 7

145

<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.

u

A2: User Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

A2-01 to

A2-32

(0106 to

0125)

User Parameters 1 to

32

User Param 1 - 32

Recently edited parameters are listed here. The user can also

select parameters to appear here for quicker access.

Default:

<1>

Range: A1-00 to

S6-07

A2-33

(0126)

User Parameter

Automatic Selection

User Parms Sel

0: Disabled

1: Enabled

0: Parameters A2-01 to A2-32 are reserved for the user to create

a list of User Parameters.

1: Save history of recently viewed parameters.

Recently edited parameters will be saved to A2-17 through

A2-32 for quicker access.

Default: 1

<2>

Range: 0, 1

<1> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<2> Default setting value is dependent on parameter A1-06. Default is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.

B.2 A: Initialization Parameters

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

255

B

Parameter List

This manual is related to the following products: