E2: motor 1 parameters, E5: pm motor settings – Yaskawa Z1000U User Manual

Page 269

background image

<4> Default setting is dependent on parameter A1-02, Control Mode Selection.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<6> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<7> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<8> When using PM motors, the default setting is determined by the motor code set to E5-01.
<9> The drive changes these settings when Auto-Tuning is performed.

u

E2: Motor 1 Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E2-01

(030E) Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps.

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated
current

<2>

122

E2-02

(030F) Motor Rated Slip

Motor Rated Slip

Sets the motor rated slip. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 Hz

Max.: 20.00 Hz

E2-03

(0310)

Motor No-Load Current No-Load Current

Sets the no-load current for the motor. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 A
Max.: E2-01

<2>

E2-04

(0311)

Number of Motor Poles Number of Poles

Sets the number of motor poles. Automatically set during

Auto-Tuning.

Default: 4

Min.: 2

Max.: 48

E2-05

(0312)

Motor Line-to-Line

Resistance

Term Resistance

Sets the phase-to-phase motor resistance. Automatically set

during Auto-Tuning.

Default:

<1>

Min.: 0.000 Ω

Max.: 65.000 Ω

E2-10

(0317)

Motor Iron Loss for

Torque Compensation

Motor Iron Loss

Sets the motor iron loss.

Default:

<1>

Min.: 0 W

Max.: 65535 W

E2-11

(0318)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power in kilowatts (1 HP = 0.746 kW).

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00 kW

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

u

E5: PM Motor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E5-01

(0329)

<1>

Motor Code Selection

(for PM Motors)

PM Mtr Code Sel

OLV/PM

OLV/PM

Enter the Yaskawa motor code for the PM motor being used.

Various motor parameters are automatically set based on the

value of this parameter. Settings that were changed manually

will be overwritten by the defaults of the selected motor code.

Note:

1. Set to FFFF when using a non-Yaskawa PM

motor or a special motor.

2. If an alarm or hunting occurs despite using a

motor code, enter the value indicated on the

nameplate.

Default:

<2>

Min.: 0000
Max.: FFFF

<4>

122

E5-02

(032A)

<1>

Motor Rated Power (for

PM Motors)

PM Mtr Capacity

OLV/PM

OLV/PM

Sets the rated capacity of the motor.

Default:

<3>

Min.: 0.10 kW

Max.: 650.00 kW

123

B.6 E: Motor Parameters

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

269