Page 152

background image

No.

Name

Setting Range

Default

b5-19

PID Setpoint Value

0.00 to 100.00%

0.00%

n

b5-20: PID Setpoint Scaling

Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04. The units for setting and display can

be changed with b5-20.

No.

Parameter Name

Setting Range

Default

b5-20

PID Setpoint Scaling

0 to 3

1

Setting 0: 0.01 Hz

The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.

Setting 1: 0.01% (100.00%: Maximum Frequency)

The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min (Set the Motor Poles)

The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined (Determined by b5-38 and b5-39)

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID

monitors U1-01 and U1-04.

n

b5-21: PID Sleep Input Source

Selects the Sleep Function characteristic action. When b5-21 is set to 1, the Sleep Function Start Level (b5-15) is compared

to the output of the drive (Speed Command after PID Block). Use this setting for open loop control.
The Sleep Function Start Level (b5-15) can be compared to the drive input or setpoint by setting b5-21 to 0.
When b5-21 is set to 2, a variation of the Sleep Function called “Snooze” is enabled. See parameters b5-22 to b5-27 for details.

No.

Parameter Name

Setting Range

Default

b5-21

PID Sleep Input Source

0 to 2

1

Setting 0: PID Setpoint
Setting 1: SFS Input
Setting 2: Snooze

n

b5-22: PID Snooze Level

Sets the PID Snooze function start level as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-22

PID Snooze Level

0 to 100%

0%

n

b5-23: PID Snooze Delay Time

Sets the PID Snooze function delay time in seconds.

No.

Parameter Name

Setting Range

Default

b5-23

PID Snooze Delay Time

0 to 2600 s

0 s

n

b5-24: PID Snooze Deactivation Level

When the PID feedback drops below this level, normal operation starts again. Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-24

PID Snooze Deactivation Level

0 to 100%

0%

n

b5-25: PID Setpoint Boost Setting

Temporary increase of PID setpoint to create an overshoot of the intended PID setpoint.

4.12 Advanced Drive Setup Adjustments

152

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual