5.9 Diagnosing and Resetting Faults

When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault, then

restart the drive.

Note:

An oC/SC fault will be displayed in the event of an IGBT failure. It may not be possible to reset this fault until the IGBT problem is corrected.

u

Fault Occurs Simultaneously with Power Loss

WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between

the ground and main circuit terminals before restarting the drive. Do not immediately operate peripheral devices if a fuse is blown or a GFCI

has tripped. Failure to comply may result in serious injury or death and will cause damage to equipment.

1.

Turn on the drive input power.

2.

Use monitor parameters U2-oo to display data on the operating status of the drive just before the fault occurred.

3.

Remove the cause of the fault and reset.

Note:

1. To find out what faults were triggered, check the fault history in U2-02. Information on drive status when the fault occurred

such as the frequency, current, and voltage can be found in U2-03 through U2-58.

Refer to Viewing Fault Trace Data

After Fault on page 218

for information on how to view fault data.

2. When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.

u

If the Drive Still has Power After a Fault Occurs
1.

Look at the HOA keypad for information on the fault that occurred.

2.

Refer to Fault Displays, Causes, and Possible Solutions on page 193

.

3.

Reset the fault.

Refer to Fault Reset Methods on page 219

.

u

Viewing Fault Trace Data After Fault

Step

Display/Result

1. Turn on the drive input power. The first screen displays.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF(AI)

Rdy

RSEQ

RREF

FWD

JOG

2. Press

to display the monitor menu screen.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

Monitor Menu

Rdy

RSEQ

RREF

FWD

JOG

3. Press

to display the monitor mode screen.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

Monitor

Rdy

RSEQ

RREF

FWD

JOG

1

4.

Press

and

to scroll to monitor U2-02. The fault code shown in U2-02

is the fault that occurred most recently. In this example, the most recent fault is

“oC” (overcurrent).

- MONITR -

U2-

02

= oC

U2-03= 60.00Hz

U2-04= 60.00Hz

DRV

Last Fault

Rdy

RSEQ

RREF

FWD

JOG

5.9 Diagnosing and Resetting Faults

218