H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

31

PID integral hold

PID Intgrl Hold

Open: Performs integral operation.

Closed: Maintains the current PID control integral value.

34

PID soft starter cancel

PID SFS Cancel

Open: PID soft starter is enabled.

Closed: Disables the PID soft starter b5-17.

35

PID input level selection PID Input Invert

Closed: Inverts the PID input signal.

40

Forward run command

(2-Wire sequence)

FwdRun 2Wire Seq

Open: Stop

Closed: Forward run

Note:

Cannot be set together with settings 42 or 43.

41

Reverse run command

(2-Wire sequence)

RevRun 2WireSeq

Open: Stop

Closed: Reverse run

Note:

Cannot be set together with settings 42 or 43.

42

Run command

(2-Wire sequence 2)

Run/Stp 2WireSeq

Open: Stop

Closed: Run

Note:

Cannot be set together with settings 40 or 41.

43

FWD/REV command

(2-Wire sequence 2)

FWD/REV 2WireSeq

Open: Forward

Closed: Reverse

Note:

Determines motor direction, but does not issue a Run command.

Cannot be set together with settings 40 or 41.

44

Offset frequency 1

Offset Freq 1

Closed: Adds d7-01 to the frequency reference.

45

Offset frequency 2

Offset Freq 2

Closed: Adds d7-02 to the frequency reference.

46

Offset frequency 3

Offset Freq 3

Closed: Adds d7-03 to the frequency reference.

47

Node setup

CanOpenNID Setup

Closed: Node setup for SI-S3 enabled.

50

Motor Pre-Heat 2

Motor Preheat 2

Closed: Triggers Motor Pre-Heat 2.

51

Sequence Timer Disable SeqTimer Disable

Closed: Drive ignores sequence timers and runs normally.

52

Sequence Timer Cancel SeqTimer Cancel

Closed: Sequence Timer Cancel .

60

Motor pre-heat 1

DCInj Activate

Closed: Triggers Motor pre-heat 1.

61

External Speed Search

command 1

Speed Search 1

Closed: Activates Current Detection Speed Search from the maximum output

frequency (E1-04).

62

External Speed Search

command 2

Speed Search 2

Closed: Activates Current Detection Speed Search from the frequency reference.

63

Field weakening

Field Weak

Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.

67

Communications test

mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the

test completes successfully.

69

Jog 2

Jog 2

Cause the drive to ramp to the jog frequency (d1-17).

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

6D

AUTO mode select

AUTO Mode Sel

Legacy Operation Mode (S5-04 = 0)
• Open: HAND reference is selected (based on S5-01)
• Closed: AUTO reference is selected (based on b1-01)
Normal Operation Mode (S5-04

≠ 0)

Note:

The drive will always be in AUTO mode at power up when

S5-04 is set to 1.

• Open: Drive is in OFF or HAND mode.
• Closed: Drive is in AUTO mode (when HAND mode select input is open)

6E

HAND mode select

HAND Mode Se

Legacy Operation Mode (S5-04 = 0)
• Open: AUTO reference is selected (based on b1-01)
• Closed: HAND reference is selected (based on S5-01)
Normal Operation Mode (S5-04

≠ 0)

Note:

The drive will always be in AUTO mode at power up when

S5-04 is set to 1.

• Open: Drive is in OFF or AUTO mode.
• Closed: Drive is in HAND mode. (when AUTO mode select input is open)

B.8 H Parameters: Multi-Function Terminals

280

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual