Starting auto-tuning, T1-01: auto-tuning mode selection, T1-02: motor rated power – Yaskawa Z1000U User Manual

Page 135: 8 auto-tuning

background image

Step

Display/Result

6.

Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency

- A.TUNE -

T1-

10

= X.XX Hz

(0.00 ~ 20.00)

PRG

Mtr Rated Slip

ESC

FWD

DATA

“X.XX Hz”

- A.TUNE -

T1-

03

= 200.0VAC

(0.0 ~ 255.0)

PRG

Rated Voltage

ESC

FWD

DATA

“200.0VAC”

Note:

1. For details on each setting,

Refer to T1: Parameter Settings during Induction Motor Auto-Tuning on page 135

.

2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.

n

Starting Auto-Tuning

WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or

serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.

WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the

motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.

NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper

operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.

Enter the required information from the motor nameplate. Press

to proceed to the Auto-Tuning start display.

Note:

These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.

Step

Display/Result

1. After entering the data listed on the motor nameplate, press

to confirm.

- A.TUNE -

0.00 Hz/ 0.00A

Tuning Ready ?

DRV

Auto-Tuning

Rdy

ESC

FWD

Press HAND key

2. Press

HAND

to activate Auto-Tuning.

flashes. The drive begins by injecting current

into the motor for about 1 min, and then starts to rotate the motor.

- A.TUNE -

X.XX Hz/ X.XXA

DRV

Tune Proceeding

Rdy

FWD

<

<<

<<< >>>

>>

>

3. Auto-Tuning finishes in approximately one to two minutes.

- MODE -

End

Tune Successful

DRV

FWD

RESET

u

T1: Parameter Settings during Induction Motor Auto-Tuning

The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.

Note:

For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change

E1-04, Maximum Output Frequency, to the desired value.

n

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used.

Refer to Auto-Tuning for Induction Motors on page 131

for details on the different

types of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2, 3

2

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving

n

T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Note:

Use the following formula to convert HP to kW: kW = HP x 0.746.

4.8 Auto-Tuning

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual