Three-phase 200 v class drive models 2 – Yaskawa Z1000U User Manual
Page 243

u
Three-Phase 200 V Class Drive Models 2o0104 to 2o0248
Table A.2 Power Ratings (Three-Phase 200 V Class) Continued
Item
Specification
Drive Model
2o0104
2o0130
2o0154
2o0192
2o0248
Maximum Applicable Motor Capacity kW (HP)
<1>
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
Input/Output
Rating
Rated Input Current (A)
<2>
95
118
140
175
226
Rated Input Capacity (kVA)
<3>
43
54
64
80
103
Rated Output Current (A)
<4> <5>
104
130
154
192
248
Overload Tolerance
120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Maximum Output Voltage (V)
Proportional to input voltage
<6>
Maximum Output Frequency (Hz)
400 Hz (User-adjustable)
Power Supply
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage Unbalance
2% or less
Harmonic Current Distortion
<6>
5% or less (IEEE519 compliant)
Input Power Factor
<6>
0.98% or more (During rated operation)
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 240 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> If one of the following specifications are needed, the maximum output voltage = [input voltage] × 0.87:
Harmonic current distortion of 5% or less
Harmonic suppression guidelines compliance
Input power factor of 0.98 or higher.
A.1 Power Ratings
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
243
A
Specifications