Yaskawa Z1000U User Manual
Page 351

Drive
Model
Terminal
For USA and Canada
For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
4o0180
R/L1, S/L2, T/L3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
25
(3)
25 to 70
(4 to 2/0)
25
(3)
25 to 70
(3 to 2/0)
M10
17.7 to 22.6
(156 to 200)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0216
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
25
(3)
25 to 95
(4 to 4/0)
35
(1)
25 to 95
(3 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0240
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0 × 2P)
M10
35
(2)
35 to 95
(2 to 4/0)
50
(1/0)
35 to 95
(1 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0302
<1>
R/L1, S/L2, T/L3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
35
(1)
35 to 150
(1 to 300)
70
(3/0)
35 to 150
(1 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0361
<1>
R/L1, S/L2, T/L3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
50
(1/0)
50 to 150
(1/0 to 300)
95
(4/0)
70 to 150
(3/0 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0414
<1>
R/L1, S/L2, T/L3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300 × 2P)
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
25 to 35
(221 to 310)
U/T1, V/T2, W/T3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300 × 2P )
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P )
M12
50
(1/0)
50 to 240
(1/0 to 400)
95
(4/0)
70 to 240
(3/0 to 400)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
<1> Take additional measures in accordance with IEC/EN 61800-5-1 when wiring an EMC filter is installed. Refer to the User Manual for details.
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2o0068 to 2o0248 and 4o0052 to 4o0414. Use only the tools recommended by the terminal
manufacturer for crimping. Yaskawa recommends UL Listed crimp terminals made by JST and Tokyo DIP (or equivalent)
matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp
terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge
and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
D.3 UL and CSA Standards
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
351
D
Standards Compliance