No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L3-05

(0493)

Stall Prevention

Selection during Run

StallP Run Sel

0: Disabled

1: Decel time

2: Decel time 2

0: Disabled. Drive runs at a set frequency. A heavy load may

cause speed loss.

1: Decel time 1. Uses the deceleration time set to C1-02 while

Stall Prevention is performed.

2: Decel time 2. Uses the deceleration time set to C1-04 while

Stall Prevention is performed.

Default: 1

Range: 0 to 2

L3-06

(0494)

Stall Prevention Level

during Run

StallP Run Level

Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive

rated current.

Default:

<2>

Min.: 30%
Max.: 150%

<2>

L3-14

(04C7)

Stall Prevention Level

during Deceleration

StallP Decel Lvl

Used when L3-04 = 1. 100% is equal to the drive rated current.

Default: 120%

Min.: 80
Max.: 120

<2>

L3-22

(04F9)

Deceleration Time at

Stall Prevention during

Acceleration

PM Acc Stall P T

Sets the deceleration time used for Stall Prevention during

acceleration in OLV/PM.

Default: 0.0 s

Min.: 0.0

Max.: 6000

L3-23

(04FD)

Automatic Reduction

Selection for Stall

Prevention during Run

CHP Stall P Sel

0: Lv1 set in L3-06

1: Autom. Reduction

0: Sets the Stall Prevention level set in L3-04 that is used

throughout the entire frequency range.

1: Automatic Stall Prevention level reduction in the constant

output range. The lower limit value is 40% of L3-06.

Default: 0

Range: 0, 1

L3-27

(0456)

Stall Prevention

Detection Time

Stl Prev DetTime

Sets the time the current must exceed the Stall Prevention level

to activate Stall Prevention.

Default: 50 ms

Min.: 0

Max.: 5000

L3-36

(11D5)

Vibration Suppression

Gain during

Acceleration (with

Current Limit)

ILim Acc Gain

Increase the setting value if oscillation occurs in the output

current during acceleration.

Default: 10.0

Min.: 0.0

Max.: 100.0

L3-39

(11D5)

Current-limited Integral

Time Constant during

Acceleration

ILim Acc I Time

Sets the time constant for acceleration rate adjustment for

current-limited acceleration.

Default: 100.0

ms

Min.: 1.0

Max.: 1000.0

L3-40

(11D6)

Current-limited

Maximum S-curve

Selection during

Acceleration

ILimAcc S-Curve

0: Disable

1: Enable

0: Disable

1: Enable

Default: 0

Range: 0, 1

L3-41

(11D7)

Vibration Suppression

Gain during

Deceleration (with

Current Limit)

ILim Dec Gain

Increase the setting value if oscillation occurs in the output

current during deceleration.

Default: 10.0

Min.: 1.0

Max.: 100.0

L3-44

(11D8)

Current-limited Integral

Time Constant during

Deceleration

ILim Dec I Time

Sets the time constant for deceleration rate adjustment for

current-limited deceleration.

Default: 100.0

ms

Min.: 1.0

Max.: 1000.0

L3-45

(11D9)

Current-limited

Maximum S-curve

Selection during

Deceleration

ILimDec S-Curve

0: Disable

1: Enable

0: Disable

1: Enable

Available when L3-04 = 6.

Default: 0

Range: 0, 1

<1> The setting range is 0, 1 in OLV/PM control mode.
<2> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(0499)

Speed Agreement

Detection Level

Spd Agree Level

Sets the frequency detection level for digital output functions

H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

L4-02

(049A)

Speed Agreement

Detection Width

Spd Agree Width

Sets the hysteresis or allowable margin for speed detection.

Default: 2.0 Hz

Min.: 0.0

Max.: 20.0

L4-03

(049B)

Speed Agreement

Detection Level (+/-) Spd Agree Lvl+-

Sets the frequency detection level for digital output functions

H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -400.0

Max.: 400.0

B.9 L: Protection Function

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual