B.7 F: Option Settings

u

F2: Analog Input Card Settings (AI-A3)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F2-01

(038F)

Analog Input Option

Card Operation

Selection

AI Function Sel

0: 3ch Individual

1: 3ch Addition

0: Option card input terminals V1, V2, and V3 replace drive

input terminals A1, A2, and A3.

1: Input signals to terminals V1, V2, and V3 are added together

to create the frequency reference.

Default: 0

Range: 0, 1

F2-02

(0368)

Analog Input Option

Card Gain

AI Input Gain

Sets the gain for the input signal to the analog card.

Default: 100.0%

Min.: -999.9

Max.: 999.9

F2-03

(0369)

Analog Input Option

Card Bias

AI Input Bias

Sets the bias for the input signal to the analog card.

Default: 0.0%

Min.: -999.9

Max.: 999.9

u

F3: Digital Input Card Settings (DI-A3)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F3-01

(0390)

Digital Input Option

Card Input Selection

DI Function Sel

0: BCD 1%

1: BCD 0.1%

2: BCD 0.01%

3: BCD 1 Hz

4: BCD 0.1 Hz

5: BCD 0.01 Hz

6: BCD(5DG) 0.01 Hz

7: Binary

0: BCD, 1% units

1: BCD, 0.1% units

2: BCD, 0.01% units

3: BCD, 1 Hz units

4: BCD, 0.1 Hz units

5: BCD, 0.01 Hz units

6: BCD customized setting (5-digit), 0.02 Hz units

7: Binary input

The unit and the setting range are determined by F3-03.

F3-03 = 0: 255/100% (-255 to +255)

F3-03 = 1: 40961/100% (-4095 to +4095)

F3-03 = 2: 30000/100% (-33000 to +33000)

When the digital operator units are set to be displayed in Hz or

user-set units (o1-03 = 2 or 3), the units for F3-01 are

determined by parameter o1-03.

Default: 0

Range: 0 to 7

F3-03

(03B9)

Digital Input Option DI-

A3 Data Length

Selection

Data length Sel

0: 8bit

1: 12bit

2: 16bit

0: 8 bit

1: 12 bit

2: 16 bit

Default: 2

Range: 0 to 2

u

F4: Analog Monitor Card Settings (AO-A3)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F4-01

(0391)

Terminal V1 Monitor

Selection

AO Ch1 Select

Sets the monitor signal for output from terminal V1. Set this

parameter to the last three digits of the desired Uo-oo

monitor. Some U parameters are available only in certain

control modes.

Default: 102

Range: 000 to 999

F4-02

(0392)

Terminal V1 Monitor

Gain

AO Ch1 Gain

Sets the gain for voltage output via terminal V1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

F4-03

(0393)

Terminal V2 Monitor

Selection

AO Ch2 Select

Sets the monitor signal for output from terminal V2. Set this

parameter to the last three digits of the desired Uo-oo

monitor. Some U parameters are available only in certain

control modes.

Default: 103

Range: 000 to 999

F4-04

(0394)

Terminal V2 Monitor

Gain

AO Ch2 Gain

Sets the gain for voltage output via terminal V2.

Default: 50.0%

Min.: -999.9

Max.: 999.9

B.7 F: Option Settings

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

271