L8-07: Output Phase Loss Protection Selection
Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.
Note:
1. Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable
this parameter in such cases.
2. Output phase loss detection is not possible when the drive is running a PM motor with light load.
No.
Name
Setting Range
Default
L8-07
Output Phase Loss Protection Selection
0 to 2
1
Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
Setting 2: Fault when Two Phases Are Lost
An output phase loss fault (LF) is triggered when two or more output phases are lost. The output shuts off and the motor coasts
to stop.
n
L8-09: Output Ground Fault Detection Selection
Enables or disables the output ground fault detection.
No.
Name
Setting Range
Default
L8-09
Output Ground Fault Detection Selection
0, 1
Determined by
o2-04
Setting 0: Disabled
Ground faults are not detected.
Setting 1: Enabled
A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
n
L8-10: Heatsink Cooling Fan Operation Selection
Selects the heatsink cooling fan operation.
No.
Name
Setting Range
Default
L8-10
Heatsink Cooling Fan Operation Selection
0, 1
0
Setting 0: Run with Timer
The fan is switched on when a Run command is active and switched off with the delay set to parameter L8-11 after releasing
the Run command. This setting extends the fan lifetime.
Setting 1: Run Always
The fan runs when power is supplied to the drive.
n
L8-11: Heatsink Cooling Fan Off-Delay Time
Sets the cooling fan switch off-delay time if parameter L8-10 is set to 0.
No.
Name
Setting Range
Default
L8-11
Heatsink Cooling Fan Off-Delay Time
0 to 300 s
60 s
n
L8-12: Ambient Temperature Setting
Automatically adapts the drive rated current to safe values when used with parameter L8-35. This eliminates the need to reduce
the drive rated current when the temperature where the drive is mounted is above the specified values.
No.
Name
Setting Range
Default
L8-12
Ambient Temperature Setting
-10 to +50 °C
40 °C