L6-03

(04A3)

Torque Detection Time

1

Torq Det 1 Time

Sets the time an overtorque or undertorque condition must exist

to trigger torque detection 1.

Default: 10.0 s

Min.: 0.0

Max.: 10.0

129

L6-13

(062E)

Motor Underload

Protection Selection

Underload Select

0: Base Freq Enable

1: Max Freq Enable

Sets the motor underload protection (ULo) based on motor

load.

0: Overtorque/undertorque detection enabled

1: Base frequency motor load enabled

Default: 0

Range: 0, 1

128

L6-14

(062F)

Motor Underload

Protection Level at

Minimum Frequency

Underload Level

Sets the UL6 detection level at minimum frequency by

percentage of drive rated current.

Default: 15%

Min.: 0

Max.: 300

128

u

L8: Drive Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-02

(04AE) Overheat Alarm Level OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature exceeds

the L8-02 level.

Default:

<1>

Min.: 50 °C

Max.: 150 °C

168

L8-03

(04AF)

Overheat Pre-Alarm

Operation Selection

OH Pre-Alarm Sel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

3: Alarm only

4: Run@L8-19 Rate

0: Ramp to stop. A fault is triggered.

1: Coast to stop. A fault is triggered.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09. A fault is triggered.

3: Continue operation. An alarm is triggered.

4: Continue operation at reduced speed as set in L8-19.

Default: 4

Range: 0 to 4

169

L8-06

(04B2)

Input Phase Detection

Level

Inp Ph Loss Lvl

When ripple is observed in the DC bus, expansion of the input

bias is calculated. This value becomes the input phase if the

difference between the maximum and minimum values of the

ripple is greater than the value set to L8-06.
Detection Level = 100% = Voltage class x

Default:

<1>

Min.: 0.0%

Max.: 50.0%

169

L8-07

(04B3)

Output Phase Loss

Protection Selection

Outp Ph Loss Det

0: Disabled

1: 1PH Loss Det

2: 2/3PH Loss Det

0: Disabled

1: Enabled (triggered by a single phase loss)

2: Enabled (triggered when two phases are lost)

Default: 1

Range: 0 to 2

170

L8-09

(04B5)

Output Ground Fault

Detection Selection

Grnd Flt Det Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default:

<1>

Range: 0, 1

170

L8-10

(04B6)

Heatsink Cooling Fan

Operation Selection

Fan On/Off Sel

0: Dur Run (OffDly)

1: Always On

0: During run only. Fan operates only during run for L8-11

seconds after stop.

1: Fan always on. Cooling fan operates whenever the drive is

powered up.

Default: 0

Range: 0, 1

170

L8-11

(04B7)

Heatsink Cooling Fan

Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run

command is removed when L8-10 = 0.

Default: 60 s

Min.: 0

Max.: 300

170

L8-12

(04B8)

Ambient Temperature

Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2

detection level.

Default: 40 °C

Min.: -10

Max.: 50

170

L8-15

(04BB)

oL2 Characteristics

Selection at Low Speeds

OL2 Sel @ L-Spd

0: Disabled

1: Enabled

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. Default: 1

Range: 0, 1

171

L8-18

(04BE)

Software Current Limit

Selection

Soft CLA Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

171

L8-19

(04BF)

Frequency Reduction

Rate during Overheat

Pre-Alarm

Fc Red dur OHAlm

Specifies the frequency reference reduction gain at overheat

pre-alarm when L8-03 = 4.

Default: 20.0%

Min.: 10.0

Max.: 100.0

171

L8-27

(04DD)

Overcurrent Detection

Gain

OC Level

Sets the gain for overcurrent detection as a percentage of the

motor rated current. Overcurrent is detected using the lower

value between the overcurrent level of the drive or the value set

to L8-27.

Default: 300.0%

Min.: 0.0

Max.: 400.0

171

B.9 L: Protection Function

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

293