beautypg.com

U: monitors, U1: operation status monitors, B.14 u: monitors – Yaskawa Z1000U User Manual

Page 309: Refer to u1: operation status, U1 - 10

background image

B.14 U: Monitors

Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.

u

U1: Operation Status Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-01

(0040)

Frequency Reference

Frequency Ref

Monitors the frequency reference. Display units are determined

by o1-03.

10 V: Max

frequency

0.01 Hz

U1-02

(0041)

Output Frequency

Output Freq

Displays the output frequency. Display units are determined by

o1-03.

10 V: Max

frequency

0.01 Hz

U1-03

(0042)

Output Current

Output Current

Displays the output current.

10 V: Drive

rated current

<1>

<2>

U1-04

(0043)

Control Method

Control Method

0: V/f Control

No signal output

available

U1-06

(0045)

Output Voltage

Reference

Output Voltage

Displays the output voltage.

10 V: 200 Vrms

<3>

0.1 Vac

U1-07

(0046)

DC Bus Voltage

DC Bus Voltage

Displays the DC bus voltage.

10 V: 400 V

<3>

1 Vdc

U1-08

(0047)

Output Power

Output kWatts

Displays the output power (this value is calculated internally).

10 V: Drive

rated power

(kW)

<4>

U1-10

(0049)

Input Terminal Status

Input Term Sts

Displays the input terminal status.

U1 - 10=

00000000

Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)

1
1
1
1
1
1
1

No signal output

available

U1-11

(004A) Output Terminal Status Output Term Sts

Displays the output terminal status.

U1 - 11=

00000000

Multi-Function

Digital Output

(terminal MD-ME-MF)

Digital Output

(terminal M1-M2)

Digital Output

(terminal M3-M4)

Multi-Function

Multi-Function

Not Used

Fault Relay

(terminal MA-MC closed

MA/MB-MC open)

1

1

1

1

0

No signal output

available

B.14 U: Monitors

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

309

B

Parameter List

This manual is related to the following products: