A.2 Drive Specifications

Note:

1. Perform rotational Auto-Tuning to obtain the performance specifications given below.
2. For optimum performance life of the drive, install the drive in an environment that meets the required specifications.

Item

Specification

Control

Character-

istics

Control Method

The following control methods can be set using drive parameters:
• V/f Control (V/f)
• Open Loop Vector Control for PM (OLV/PM)

Frequency Control Range

0.01 to 400 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max output frequency (-10 to +40 °C)

Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C)

Frequency Setting Resolution Digital inputs: 0.01 Hz

Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)

Output Frequency Resolution 0.001 Hz

Frequency Setting Signal

Main speed frequency reference: DC -10 to +10 V (20 kΩ), DC 0 to +10 V (20 kΩ),

4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)

Starting Torque

V/f: 150% at 3 Hz
OLV/PM: 100% at 3 Hz

<1>

Speed Control Range

V/f: 1:40

OLV/PM: 1:20

Speed Control Accuracy

V/f: ±0.2 to 3% (25 °C ±1 0°C)
OLV/PM: ±0.2% (25 °C ±10 °C)

<2>

Speed Response

OLV/PM: 10 Hz (25 °C ±10 °C)

Accel/Decel Time

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking Torque

Same value as overload tolerance in motoring or regeneration.

V/f Characteristics

User-selected programs and V/f preset patterns possible

Main Control Functions

Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection, 4 Step Speed

(max), Accel/Decel Switch, S-curve Accel/decel, 3-Wire Sequence, Auto-Tuning (Stationary for Line-

to-Line Resistance, Rotational for V/f Control), Cooling Fan on/off Switch, Slip Compensation, Torque

Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking

at Start and Stop, Overexcitation Braking, PID Control (with sleep function), Energy Saving Control,

APOGEE FLN Comm. (RS-422/RS-485 4.8 kbps), BACnet Comm. (RS-485 max. 76.8 kbps),

MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Metasys N2 Comm. (RS-422/RS-485

9.6 kbps), Fault Restart, Application Presets, Overexcitation Deceleration, Sequence Timer Operation,

Secondary PI Control, Bypass Operation, HOA Keypad, Dynamic Noise Control

Protection

Functions

Power Supply Regeneration Available

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when output current reaches about 200% of the rated current

Overload Protection

Drive stops after 60 s at 150% of rated output current

<3>

Overvoltage Protection

200 V class: Stops when input voltage exceeds approx. 315 V

400 V class: Stops when input voltage exceeds approx. 630 V

Undervoltage Protection

200 V class: Stops when input voltage falls below approx. 150 V

400 V class: Stops when input voltage falls below approx. 300 V

Momentary Power Loss

Ride-Thru

Immediately stop after 2 ms or longer power loss

<4>

Continuous operation during power loss than 2 s (standard)

<5>

Heatsink Overheat Protection Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<6>

Charge LED of Capacitor for

Control Power Supply

Remains lit until control power supply voltage falls below 50 V

A.2 Drive Specifications

246

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual