n

Auto-Tuning for Permanent Magnet Motors

Automatically sets the V/f pattern and motor parameters E1-oo and E5-oo when a PM motor is used.

Table 4.21 Types of Auto-Tuning for Permanent Magnet Motors

Type

Setting

Application Conditions and Benefits

Control Mode

OLV/PM

PM Motor Parameter

Settings

T2-01 = 0

• Motor does not rotate during Auto-Tuning.
Motor test report or motor data similar to

Table 4.22

are available.

YES

PM Stationary Auto-Tuning

T2-01 = 1

• A motor test report listing motor data is not available.
• Drive automatically calculates and sets motor parameters.

YES

PM Stationary Auto-Tuning

for Stator Resistance

T2-01 = 2

• Useful to tune the drive when the motor data were set up manually or by motor

code and the cable is longer than 50 m.

• Should also be performed if the cable length has changed after prior tuning.

YES

PM Rotational Auto-Tuning

T2-01 = 14

• A motor test report listing motor data is not available.
• Motor can be decoupled from the load and rotate freely while Auto-Tuning

is performed. Drive automatically calculates and sets motor parameters.

• PM Rotational Auto-Tuning gives more accurate results than Stationary

Auto-Tuning.

YES

Table 4.22

lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.

The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor

manufacturer. Also refer to page

110

for details on the Auto-Tuning process and selection.

Table 4.22 Auto-Tuning Input Data

Input Value

Input Parameter

Unit

Tuning Type (T2-01)

0

Motor Parameter

Settings

Control Mode

A1-02

5

Motor Code (Hex.)

T2-02

<1>

Motor Type

T2-03

Motor Rated Power

T2-04

kW

YES

Motor Rated Voltage

T2-05

Vac

YES

Motor Rated Current

T2-06

A

YES

Motor Rated Frequency

T2-07

Hz

YES

Number of Motor Poles

T2-08

YES

Stator Single-phase Resistance

T2-10

Ω

YES

d-Axis Inductance

T2-11

mH

YES

q-Axis Inductance

T2-12

mH

YES

Induced Voltage Constant Unit Selection

<2>

T2-13

mVs/rad (elec.)

YES

Voltage Constant

<2>

<3>

T2-14

mVmin (mech.)

YES

Tuning Pull-in Current

T2-15

A

<1> Input the motor code when using a Yaskawa motor. Select “FFFF” when using a motor from another manufacturer.
<2> It is only necessary to input either T2-13 or T2-14. Select one and leave the other empty.
<3> Dependent upon T2-13 setting.

u

Before Auto-Tuning the Drive

Check the items below before Auto-Tuning the drive.

n

Basic Auto-Tuning Preparations

• Auto-Tuning requires the user to input data from the motor nameplate or motor test report. Make sure this data is available

before Auto-Tuning the drive.

• For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.

Note:

Better performance is possible when using a motor with a base voltage that is lower than the input supply voltage (20 V for 200 V class

models and 40 V for 400 V class models). This is particularly important when operating the motor above 90% of base speed, where high

torque precision is required.

4.8 Auto-Tuning

132

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual