H4: analog outputs – Yaskawa Z1000U User Manual
Page 286
H3 Multi-Function Analog Input Settings
H3-oo
Setting
Function
LCD Display
Description
Page
E
Motor temperature (PTC
input)
Motor PTC
10 V = 100%
–
F
Through mode
Not Used
Set this value when using the terminal in the pass-through mode.
–
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
–
25
Secondary PI Setpoint
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
–
26
Secondary PI Feedback PI2 Feedback
10 V = S3-02 (maximum output frequency)
–
u
H4: Analog Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H4-01
(041D)
Multi-Function Analog
Output Terminal FM
Monitor Selection
Term FM FuncSel
Selects the data to be output through multi-function analog
output terminal FM.
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter “103” for U1-03.
Default: 102
Range: 000 to
655
–
H4-02
(041E)
Multi-Function Analog
Output Terminal FM
Gain
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Default: 100.0%
Min.: -999.9
Max.: 999.9
–
H4-03
(041F)
Multi-Function Analog
Output Terminal FM
Bias
Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
–
H4-04
(0420)
Multi-Function Analog
Output Terminal AM
Monitor Selection
Terminal AM Sel
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter “103” for U1-03.
Default: 103
Range: 000 to
655
–
H4-05
(0421)
Multi-Function Analog
Output Terminal AM
Gain
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of
the selected monitor value.
Default: 50.0%
Min.: -999.9
Max.: 999.9
–
H4-06
(0422)
Multi-Function Analog
Output Terminal AM
Bias
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
–
H4-07
(0423)
Multi-Function Analog
Output Terminal FM
Signal Level Selection
Level Select1
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0 to 10 V
1: -10 to +10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
–
H4-08
(0424)
Multi-Function Analog
Output Terminal AM
Signal Level Selection
AO Level Select2
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0 to 10 V
1: -10 to +10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
–
B.8 H Parameters: Multi-Function Terminals
286
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual