HOA Keypad Display

Fault Name

oL4

Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the

allowable time (L6-06).

HOA Keypad Display

Fault Name

oL5

Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.

HOA Keypad Display

Fault Name

oPr

HOA Keypad Connection Fault
The HOA keypad has been disconnected from the drive.

An oPr fault will occur when all of the following conditions are true:
• Output is interrupted when the keypad is disconnected (o2-06 = 1).
• The Run command is assigned to the keypad (b1-02 = 0 and OFF mode has been selected).

Cause

Possible Solution

External operator is not properly connected to the

drive

• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply

drive input power.

HOA Keypad Display

Fault Name

ov

Control Circuit Overvoltage
Voltage in the control circuit has exceeded the overvoltage level.
• For 200 V class drives: approximately 450 V
• For 400 V class drives: approximately 900 V

Cause

Possible Solution

HOA Keypad Display

Fault Name

SCF

Safety Circuit Fault
Safety Circuit Fault is detected.

HOA Keypad Display

Fault Name

SEr

Too Many Speed Search Restarts
The number of Speed Search restarts exceeded the value set to b3-19.

Cause

Possible Solution

Parameters related to Speed Search are set to the

wrong values

• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).

The motor is coasting in the opposite direction of

the Run command

Set b3-14 to 1 to enable Bi-Directional Speed Search.

Digital Operator Display

Fault Name

SoH

Snubber Discharge Resistor Overheat

Digital Operator Display

Fault Name

SrC

Phase Order Detection Fault
The phase rotation direction for the input power supply changed.

Digital Operator Display

Fault Name

Srr

Internal Resistance Fault
An operation failure occurred in the snubber discharge resistor circuit.

HOA Keypad Display

Fault Name

STo

Motor Pull Out or Step Out Detection
Motor pull out or step out has occurred. Motor has exceeded its pull-out torque.

Cause

Possible Solution

5.4 Fault Detection