Yaskawa Z1000U User Manual
Page 137

n
T2-01: PM Motor Auto-Tuning Mode Selection
No.
Name
Setting Range
Default
T2-01
PM Motor Auto-Tuning Mode Selection
0 to 2; 14
0
Setting 0: PM Motor Parameter Settings
Setting 1: PM Stationary Auto-Tuning
Setting 2: PM Stationary Auto-Tuning for Stator Resistance
Setting 14: PM Rotational Auto-Tuning
n
T2-02: PM Motor Code Selection
If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code in T2-02 to
automatically set parameters T2-03 through T2-14. If the drive is operating a specialized motor or a motor designed by a
manufacturer other than Yaskawa, set T2-02 to FFFF and enter the data from the motor nameplate or the motor test report as
prompted.
Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ depending on the
selected control mode.
No.
Name
Setting Range
Default
T2-02
PM Motor Code Selection
0000 to FFFF
Determined by A1-02
and o2-04
n
T2-03: PM Motor Type
Selects the type of PM motor the drive will operate.
No.
Name
Setting Range
Default
T2-03
PM Motor Type
0, 1
1
Setting 0: IPM motor
Setting 1: SPM motor
n
T2-04: PM Motor Rated Power
Specifies the motor rated power in kilowatts.
No.
Name
Setting Range
Default
T2-04
PM Motor Rated Power
0.00 to 650.00 kW
Determined by o2-04
n
T2-05: PM Motor Rated Voltage
Sets the motor rated voltage.
No.
Name
Setting Range
Default
T2-05
PM Motor Rated Voltage
0.0 to 255.0 V
<1>
200.0 V
<1>
<1> Value shown is specific to 200 V class drives. Double value for 400 V class drives.
n
T2-06: PM Motor Rated Current
Enter the motor rated current in amps.
No.
Name
Setting Range
Default
T2-06
PM Motor Rated Current
0.0% to 300.0% of the
drive rated current.
Determined by o2-04
n
T2-07: PM Motor Base Frequency
Enter the motor base frequency in Hz.
Note:
T2-07 will be displayed when in OLV/PM.
No.
Name
Setting Range
Default
T2-07
PM Motor Base Frequency
0.0 to 400.0 Hz
87.5 Hz
4.8 Auto-Tuning
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual
137
4
Start-Up Programming & Operation