beautypg.com

Yaskawa Z1000U User Manual

Page 164

background image

Setting

Function

Page

4

Output Voltage Bias

5

Accel/Decel Time Gain

6

DC Injection Braking Current

7

Overtorque/Undertorque Detection Level

8

Stall Prevention Level During Run

9

Output Frequency Lower Limit Level

B

PID Feedback

164

Setting

Function

Page

C

PID Setpoint

164

D

Frequency Bias

164

E

Motor Temperature (PTC Input)

164

F

Through Mode

164

16

Differential PID Feedback

164

25

Secondary PI Setpoint

164

26

Secondary PI Feedback

164

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input

terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog

input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 157

for details.

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 157

for details.

Setting B: PID Feedback

Supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.

Setting C: PID Setpoint

Supplies the PID setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PID setpoint.

PID operation to be enabled in b5-01 to use this setting.

Setting D: Frequency Bias

The input value of an analog input set to this function will be added to the frequency reference. This function can be used with

any frequency reference source.

Setting E: Motor Temperature

In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient) thermistor

for motor insulation protection.

Setting F: Through Mode

When set to F, an input does not affect any drive function, but the input level can still be read out by a PLC via APOGEE

FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 communications.

Setting 16: Differential PID Feedback

If an analog value is set for this function, the PID controller is set for differential feedback. The difference of the PID feedback

input value and the differential feedback input value builds the feedback value used to calculate the PID input.

Setting 25: Secondary PI Setpoint

10 V = S3-02 (Maximum Output Frequency).

Setting 26: Secondary PI Feedback

10 V = S3-02 (Maximum Output Frequency).

4.12 Advanced Drive Setup Adjustments

164

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

This manual is related to the following products: