Communication data error occurred due to noise

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or

the drive input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors

if required.

• Separate all communication wiring from drive power lines.

HOA Keypad Display

Fault Name

CoF

Current Offset Fault

Cause

Possible Solution

The drive tried to adjust the current offset value

beyond the allowable range. This is due to residual

induction current in the motor (e.g., during sudden

deceleration or when coasting) when the drive

attempted to start the motor.

• Create a motor restart sequence that allows enough time for residual induction voltage to dissipate.
• Enable Speed Search at start (b3-01 = 1). Use the multi-function terminals to execute External

Speed Search 1 and 2 (H1-oo = 61 or 62).

Note:

When using a PM motor, External Speed Searches 1 and 2 perform the same operation.

The current sensor in the drive is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF00 to CPF03, CPF07, CPF08, CPF11 to

CPF14, CPF16 to CPF24

CPF26 to CPF35

CPF40 to CPF45

Control Circuit Error

HOA Keypad Display

Fault Name

CPF06

EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution

There is an error in EEPROM control circuit

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

The power supply was switched off while

parameters were being saved to the drive

Reinitialize the drive using parameter A1-03.

HOA Keypad Display

Fault Name

CPF25

Terminal Board Not Connected

Cause

Possible Solution

Terminal board is not connected correctly

Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

HOA Keypad Display

Fault Name

doH

Damping Resistor Overheat
The temperature of the built-in damping resistor exceeded the set value.

HOA Keypad Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the PLC and

F6-03 is set to a value other than 3

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

HOA Keypad Display

Fault Name

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.