Setting 0: Count Successful Restarts

The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is

repeated each time a fault occurs until the counter reaches the value set to L5-01.

Setting 1: Count Restart Attempts

The drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts to

restart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds the

value set to L5-01, the drive stops attempting to restart.

n

L6-13: Motor Underload Protection Selection

Sets Motor Underload Protection (UL6) based on motor load and determines whether the level of L6-02 refers to fbase or

fmax.
Selects the operation of underload detection UL6. Underload is detected when the output current falls below the underload

detection level defined by L6-14 and L2-02.

No.

Name

Setting Range

Default

L6-13

Motor Underload Protection Selection

0, 1

0

Setting 0: Fbase Motor Load Enabled
Setting 1: Fmax Base Motor Load Enabled

UL Detection Level

L6-02

(0 to 300%)

0

Fmin

Fbase

1/f

Fmax

Output
Frequency

L6-14

Motor Underload

Protection at Fmin

Figure 4.36 Motor Underload Protection

n

L6-14: Motor Underload Protection Level at Minimum Frequency

Sets the UL6 detection level at minimum frequency by percentage of drive rated current

No.

Name

Setting Range

Default

L6-14

Motor Underload Protection Level at Minimum Frequency

0 to 300%

15%

n

L8-02: Overheat Alarm Level

Sets the overheat alarm (oH) detection level.
The drive outputs an alarm when the heatsink temperature exceeds the overheat alarm level. If the drive is set to continue

operation after this alarm occurs (L8-03 = 4) and the temperature reaches the overheat fault level, the drive will trigger an oH1

fault and stop operation.
When an output terminal is set for the oH pre-alarm (H2-oo = 20), the switch will close when the heatsink temperature rises

above L8-02.

No.

Name

Setting Range

Default

L8-02

Overheat Alarm Level

50 to 150 °C

Determined by

o2-04

4.12 Advanced Drive Setup Adjustments

168

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual