Operation time (minutes)

Cold start
(characteristics when an
overload occurs at a
complete stop)

Hot start
(characteristics when an
overload occurs during
continuous operation at 100%)

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200

Figure D.6 Motor Overload Protection Time

n

L1-03: Motor Overheat Alarm Operation Selection (PTC input)

Sets the drive operation when the PTC input signal reaches the motor overheat alarm level (oH3).

No.

Name

Setting Range

Default

L1-03

Motor Overheat Alarm Operation Selection (PTC input)

0 to 3

3

Setting 0: Ramp to Stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.

Setting 1: Coast to Stop

The drive output is switched off and the motor coasts to stop.

Setting 2: Fast Stop

The drive stops the motor using the Fast Stop time set in parameter C1-09.

Setting 3: Alarm Only

The operation is continued and an oH3 alarm is displayed on the digital operator.

n

L1-04: Motor Overheat Fault Operation Selection (PTC input)

Sets the drive operation when the PTC input signal reaches the motor overheat fault level (oH4).

No.

Name

Setting Range

Default

L1-04

Motor Overheat Fault Operation Selection (PTC input)

0 to 2

1

Setting 0: Ramp to Stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.

Setting 1: Coast to Stop

The drive output is switched off and the motor coasts to stop.

Setting 2: Fast Stop

The drive stops the motor using the Fast Stop time set in parameter C1-09.

D.3 UL and CSA Standards

356

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual