Page 150

background image

No.

Parameter Name

Setting Range

Default

b5-09

PID Output Level Selection

0, 1

0

Setting 0: Normal Output

A positive PID input causes an increase in the PID output (direct acting).

Setting 1: Reverse Output

A positive PID input causes a decrease in the PID output (reverse acting).

n

b5-10: PID Output Gain Setting

Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01 = 3

or 4).

No.

Name

Setting Range

Default

b5-10

PID Output Gain Setting

0.00 to 25.00

1.00

n

b5-11: PID Output Reverse Selection

Determines whether a negative PID output reverses the direction of drive operation. This parameter has no effect when the

PID function trims the frequency reference (b5-01 = 3 or 4) and the PID output will not be limited (same as b5-11 = 1).

No.

Parameter Name

Setting Range

Default

b5-11

PID Output Reverse Selection

0, 1

0

Setting 0: Reverse Disabled

Negative PID output will be limited to 0 and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PID output will cause the drive to run in the opposite direction.

n

b5-12: PID Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

No.

Parameter Name

Setting Range

Default

b5-12

PID Feedback Loss Detection Selection

0 to 5

0

Setting 0: Digital Output Only

A digital output set for “PID feedback low” (H2-oo = 3E) will be triggered if the PID feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-oo = 3F) will be

triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a

fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output resets when the feedback

value leaves the loss detection range.

Setting 1: Feedback Loss Alarm

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low”

alarm will be displayed and a digital output set for “PID feedback low” (H2-oo = 3E) will be triggered. If the PID feedback

value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed

and a digital output set for “PID feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output

(H1-oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection

range.

Setting 2: Feedback Loss Fault

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low”

fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH

- Feedback High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the

motor.

Setting 3: Digital Output Only, even if PID Is Disabled by Digital Input

Same as b5-12 = 0. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

Setting 4: Feedback Loss Alarm, even if PID Is Disabled by Digital Input

Same as b5-12 = 1. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

4.12 Advanced Drive Setup Adjustments

150

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual