Yaskawa Z1000U User Manual
Page 174

Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units (100% = Max Output Frequency)
Setting 2: r/min Units (Calculated by the Max Output Frequency and the Number of Motor Poles)
Setting 3: User-set Units (Use o1-10, o1-11)
Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to
o1-11.
For example, to have the maximum output frequency displayed as “100.00”, set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with
2 decimal points).
Note:
1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-16: output frequency after softstarter (accel/decel ramp generator)
d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04 and E5-04.
n
o1-06: User Monitor Selection Mode
Normally the monitors shown directly below the active monitor are the next two sequential monitors. If o1-06 (User Monitor
Selection Mode) is set to 1: “3 Mon Selectable”, those two monitors are locked as specified by parameters o1-07 and o1-08
and will not change as the top parameter is scrolled with the Up/Down Arrow keys.
No.
Name
Setting Range
Default
o1-06
User Monitor Selection Mode
0, 1
<1>
<1> Default is 0 when b5-01 is set to 0.
Default is 1 when b5-01 is set to 1 or 3.
Setting 0: 3 Monitor Sequential (Displays the Next 2 Sequential Monitors)
Setting 1: 3 Monitor Selectable (o1-07, and o1-08 Selected Monitor Is Shown)
n
o1-07: Second Line Monitor Selection
Selects which monitor will be displayed in the second line. The monitor parameter number is entered into the spaces provided:
Uo-oo.
For example, set “403” to display monitor parameter U4-03.
No.
Name
Setting Range
Default
o1-07
Second Line Monitor Selection
101 to 699
<1>
<1> Default is 102 when b5-01 is set to 0.
Default is 504 when b5-01 is set to 1 or 3.
n
o1-08: Third Line Monitor Selection
Selects which monitor will be displayed in the third line. The monitor parameter number is entered into the spaces provided:
Uo-oo.
For example, set “403” to display monitor parameter U4-03.
No.
Name
Setting Range
Default
o1-08
Third Line Monitor Selection
101 to 699
<1>
<1> Default is 102 when b5-01 is set to 0.
Default is 501 when b5-01 is set to 1 or 3.
n
o1-09: Frequency Reference Display Units
Sets unit display for the frequency reference parameters and frequency related monitors when o1-03 > 40.
No.
Name
Setting Range
Default
o1-09
Frequency Reference Display Units
0 to 16
16
4.12 Advanced Drive Setup Adjustments
174
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual