D.2 European Standards

Figure D.1 CE Mark

The CE mark indicates that a product is in compliance with applicable European Directives for safety and environmental

regulations. It is required for engaging in business and commerce in Europe.
The applicable European Directives for this product are as follows. We declared the CE marking based on the harmonized

standards in

Table D.1

.

Table D.1 European Directives

Applicable European Directive

Applicable Harmonized Standards

Low Voltage Directive (2006/95/EC)

IEC/EN618995-1: 2007

EMC Guidelines (2004/108/EC)

IEC/EN 61800-3: 2004

Machinery Directive (2006/42/EC)

ISO/EN ISO 13849-1/AC: 2009

IEC/EN 62061: 2005 (SILCL3)

IEC/EN 61800-5-2: 2007 (SIL3)

The user(s) is solely responsible for ensuring that the end products used with this drive comply with all applicable European

directives and with other national regulations (if required).

u

CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage

Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other

devices:

n

Area of Use

Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

Refer to Enable the Internal EMC Filter on page 77

for details.

n

Guarding Against Harmful Materials

When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive

from above or below.

u

EMC Guidelines Compliance

Models ZooEoooo and ZooWoooo have built-in EMC filters, are tested according to European standards IEC/EN

61800-3: 2004, and comply with EMC guidelines. Use drives with built-in EMC filters to comply with EMC guidelines.

n

EMC Filter Installation

Installation Method

Verify the following installation conditions to ensure that other devices and machinery used in combination with drive models

ZooEoooo and ZooWoooo also comply with EMC guidelines.

1.

Place the drive in the enclosure.

2.

Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.

3.

Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.